The Effect of Air Change Rates on the Heating and Cooling Energy Performance of Educational Buildings According to TS 825: 2024 Standard
DOI:
https://doi.org/10.5281/zenodo.21639276Keywords:
TS 825 (2024), air change rate, building energy performance, ventilation heat lossAbstract
This study investigates the impact of outdoor air change rates on the monthly and annual specific energy consumption of an educational building. The Faculty of Engineering building at Yalova University was used as a case study. The parametric analyses were conducted across four fresh air scenarios = 0.35, 0.70, 1.05 and 1.40 m3/h.m2) based on the TS 825:2024 calculation method. The results indicate that increasing the air change rate from the lowest to the highest scenario elevates the total annual specific energy consumption by approximately 31% (from 100.8 to 132.2 kWh/m².a). This effect is highly dominant during the winter heating season due to low outdoor temperatures. Compared to the standard reference value of 0.70 m3/h.m2 higher ventilation rates increase energy demands by 9% to 18%, demonstrating that excessive fresh air intake directly reduces building energy efficiency. The critical need for demand-controlled ventilation or heat recovery systems is to maintain indoor air quality without increasing thermal loads.
References
M. Altun, C. M. Akgul, and A. Akcamete, “Effect of envelope insulation on building heating energy requirement, cost and carbon footprint from a life cycle perspective,” Journal of the Faculty of Engineering and Architecture of Gazi University, vol. 35, no. 1, pp. 147–163, 2020, doi: 10.17341/gazimmfd.445751.
M. Altun, A. Akçamete, and Ç. Meral Akgül, “Investigation of the effect of outdoor temperature data on the building heating energy requirement and validity of the TS 825 degree-day region clustering,” Pamukkale University Journal of Engineering Sciences, vol. 26, no. 6, pp. 1062–1075, 2020, doi: 10.5505/pajes.2019.00334.
D. Evin and A. Ucar, “Energy impact and eco-efficiency of the envelope insulation in residential buildings in Turkey,” Appl. Therm. Eng., vol. 154, pp. 573–584, May 2019, doi: 10.1016/j.applthermaleng.2019.03.102.
M. Balat, “Security of energy supply in Turkey: Challenges and solutions,” Energy Convers. Manag., vol. 51, no. 10, pp. 1998–2011, Oct. 2010, doi: 10.1016/j.enconman.2010.02.033.
A. Senturk and M. Ozcan, “Nearly zero energy building design and optimization: A residential building transformation in Türkiye,” Energy Exploration and Exploitation, vol. 42, no. 3, pp. 997–1026, May 2024, doi: 10.1177/01445987231219765.
Selçuk Usta, “Comparison of Insulated and Uninsulated Versions of a Building Located at Second Region According to TS 825 “Guidelines for Heat Insulation in Buildings,” Electronic Journal of Construction Technologies, vol. 01, no. 05, pp. 1–24, 2009, [Online]. Available: www.teknolojikarastirmalar.com
“Turkish Standart TS 825 Thermal insulation requirements for buildings,” Oct. 2024. [Online]. Available: www.tse.org.tr
T. Türel, S. N. Erkara, A. Kuruçay, Ş. Eren, M. C. Uzun, and Ü. Ünver, “An Experimental Approach to Investigate the Effects of Infiltration Losses on Building Energy Performance,” ZeroBuild Journal, vol. 02, no. 01, pp. 99–114, 2024, doi: 10.5281/zenodo.10565245.